Order number 335272
Max. Output [LTP] [kVA/kw] |
19.6/15.7 |
Prime power (PRP) [kVA/kW] |
17.9/14.3 |
Alternator type |
eco40 1l4 c |
Nominal voltage [V] |
400/230 |
Nominal current 3~ (PRP) [A] |
25,8 |
Power factor cos (phi) |
0,8 |
Frequency [Hz] |
50 |
Voltage regulation |
Mecc Alte ECO40 1L4 C |
Engine |
|
---|---|
Brand |
Volvo |
Model |
4TNV88-BIGE |
Emission regulation |
Stage V |
Cooling system |
wassergekühlt |
Displacement [ccm] |
2190 |
Engine output (ESP) [kW] |
22 |
Engine output (PRP) [kW] |
17,2 |
RPM [U/min] |
1500 |
RPM regulation |
mechanisch |
Fuel |
Diesel |
Fuel tank capacity [l] |
190 |
Fuel consumption @ 75% PRP [L/h] |
4,2 |
Fuel consumption @ 100% PRP [L/h] |
5,5 |
Running time @ 75% PRP |
44,9 |
Starting system |
Elektrostart |
Electric circuit |
12 |
Sound power level LWA [db(A)] |
96 |
Sound pressure level LPA (7 m) [db(A)] |
71 |
Shockproof sockets |
1x CEE 400V / 63A 1x CEE 400V / 32A 1x CEE 400V / 16A 1x 230V / 16A Klemmleiste |
- Soundproofed hood - extra quiet
- Engine according to Emissions Stage V
- Manual/Automatic instrument panel in IP 54
- Base frame with continuous fork-lift plates and ram protection
- Galvanised hood for increased corrosion protection
- Large tank for long running times
- Outlet for external refuelling incl. a three-way fuel tap
- Liquid collecting tray to protect the environment
- Problem-free use, also in winter through use of a standard engine and coolant prewarming
- The main battery switch
- Manual oil scavenger pump
- Remote start connection
- Diesel filter with water trap
- Terminal board (Omission with socket combination 3)
- Hot engine parts protection
- Document bag
Socket combination 2 with RCD Type B (incl. terminal board) |
Article number: auf Anfrage |
Socket combination 3 with RCD Type B (terminal board will be removed / incl. Insulation monitoring) |
Article number: 342 036 |
Supplying power to a building IT/TN |
Article number: 342 232 |
Insulation monitoring |
Article number: 163 076 |
Potential-free contact |
Article number: 342 030 |
Twilight switch |
Article number: 342 032 |
Remote control panel |
Article number: E135 961 |
E-RMA SIM remote monitoring |
Article number: 342 220 |
E-RMA LAN remote monitoring |
Article number: 342 221 |
Dummy-Load |
Article number: auf Anfrage |
Special colour |
Article number: auf Anfrage |
Chassis ST rigid |
Article number: 351 106 |
Chassis HV height adjustable |
Article number: 351 107 |
Float switch (start/stop) 10m |
Article number: 342 033 |
Load transfer switch |
Article number: 343 016R |
Maintenance package 500 h |
Article number: auf Anfrage |
Similar products
ESE 20 YW/RS | |
Power [kVA/kW] | 17.9/14.3 |
---|---|
Nominal voltage [V] | 400/230 |
Weight in [kg] | 985 |
Dimensions L x W x H [mm] | 2280x950x1200 |
ESE 35 YW/RS | |
Power [kVA/kW] | 30.5/24.4 |
---|---|
Nominal voltage [V] | 400/230 |
Weight in [kg] | 1105 |
Dimensions L x W x H [mm] | 2280x1040x1200 |
ESE 45 YW/RS | |
Power [kVA/kW] | 42.0/33.6 |
---|---|
Nominal voltage [V] | 400/230 |
Weight in [kg] | 1140 |
Dimensions L x W x H [mm] | 2280x1040x1200 |